Sample COMTRADE files (free download)

Four COMTRADE records for testing a reader, teaching, or learning to read fault and power-quality data. Each comes as a .cfg + .dat pair (ASCII) and as a single .cff file, written to IEEE C37.111-2013.

These records are synthetic: generated from a model, not recorded on any real network. Station and device names are illustrative. They are free to use for any purpose, including commercial use, with no attribution required (CC0 1.0).

A-phase-to-ground fault on a 132 kV line

A single-line-to-ground fault: A-phase voltage sags to about 48% for about five cycles, residual current appears, and the breaker trip contact operates. Six analog channels, two status channels, 4.8 kHz, 0.5 s.

FileFDR-2214_AG-FAULT
Station · deviceASHFORD 132kV · SEL-411L / REC-01
Channels6 analog, 2 status
Sampling4.8 kHz at 50 Hz, 2400 samples

Download: .cfg · .dat · .cff Open in SagSwell

Upstream sag at a 22 kV industrial feeder

The same upstream fault seen from a distribution feeder: a sag to about 67% on all three phases. Useful for IEEE 1159 classification and the ITIC curve. 3.2 kHz, 0.85 s.

FilePQM-07_SAG-68PCT
Station · devicePARK ROYAL IND. EST. 22kV · PQM-3000 / FEEDER 07
Channels6 analog, 2 status
Sampling3.2 kHz at 50 Hz, 2720 samples

Download: .cfg · .dat · .cff Open in SagSwell

Shallow sag at a 400 V motor control centre

A shallow sag to about 86% at low voltage, recorded at the same moment as the two records above, so the three can be lined up on one timeline. 3.2 kHz, 0.9 s.

FilePQM-22_MCC-SAG-865
Station · devicePARK ROYAL MCC-2 400V · PQM-3000 / MCC BUS
Channels6 analog, 2 status
Sampling3.2 kHz at 50 Hz, 2880 samples

Download: .cfg · .dat · .cff Open in SagSwell

Harmonic distortion on a variable-speed-drive bus

Steady-state distortion at a 400 V bus feeding drives: no disturbance, a spectrum to study, THD and the IEEE 519 limits. 6.4 kHz, 1.2 s.

FilePQM-11_VSD-HARMONICS
Station · deviceTILBURY DOCKS 400V MCC · PQM-3000 / VSD BUS
Channels6 analog, 2 status
Sampling6.4 kHz at 50 Hz, 7680 samples

Download: .cfg · .dat · .cff Open in SagSwell

What you can do with them

  • Check that a COMTRADE reader or your own parser handles the 2013 format, ASCII data and the single-file .cff.
  • Teach: the first three records show one upstream fault seen from three buses at three voltage levels.
  • Practise reading a record: IEEE 1159 sags, the ITIC curve and harmonics.

New to the format? See the COMTRADE file format explained.